PANASONIC · 3-PIPE ECOi EX
U-8MF3E8
8 HP
22,4 kW cooling
25,0 kW heating
R410A
A++ efficiency
HR
Eurovent: 19.02.001
Eurovent ✓
PANASONIC U-8MF3E8 is a heat recovery VRF outdoor unit with a cooling capacity of 8 HP (22,4 kW). It uses R410A refrigerant and has SEER 7,00 / SCOP 4,80 efficiency ratings. It offers a cooling sound power of 79,0 dB(A), a 1180×1842×1000 mm body. It is ranked #83 by SEER among 160 models in the 8 HP class (class average SEER 7,03).
8 HP class
160 models
SEER rank: 83
Class avg. SEER 7,03
Highest 8,90
Performance
| Cooling | |
|---|---|
| Nominal capacity | 22,40 kW |
| Power input | 7,23 kW |
| EER (rated) | 3,10 |
| SEER (seasonal) ℹ | 7,00 |
| Heating | |
| Nominal capacity | 25,00 kW |
| Power input | 4,76 kW |
| COP (rated) | 5,25 |
| SCOP (seasonal) ℹ | 4,80 |
| Test configuration | |
| Indoor unit combination | 4x S-56MU2E5C (Cassette) |
Physical & Environmental
| General | |
|---|---|
| System type | HR (Heat Recovery) |
| Cooling type | Air-cooled |
| Combination | Possible |
| Refrigerant | R410A |
| Power supply | 400-3-50 |
| Max. indoor units | — |
| Air flow | 12.600 m³/h |
| Fan count | 1 |
| Dimensions & Weight | |
| Dimensions (H×W×D) | 1842 × 1180 × 1000 mm |
| Weight | 261 kg |
| Sound (LwA) | |
| In cooling | 79,0 dB(A) |
| In heating | 77,0 dB(A) |
| Operating temperature | |
| Cooling range | -10°C ÷ 52°C |
| Heating range | -20°C ÷ 18°C |
Üstten görünüş
Ölçüler mmYükseklik: 1.842 mm
⚡ Energy simulation for this unit
Alternative models in the 8 HP class
Top models at the same capacity, ranked by SEER. This unit is highlighted.
8,90
8,81
8,73
8,70
8,67
8,31
7,00
Other models in the same series (8 models)
PANASONIC
U-8MF4E8
19,5 kW
SEER 6,2
PANASONIC
U-10MF4E8
24,4 kW
SEER 6,5
PANASONIC
U-10MF3E8
28,0 kW
SEER 7,0
PANASONIC
U-12MF4E8
29,3 kW
SEER 6,3
PANASONIC
U-12MF3E8
33,5 kW
SEER 6,4
PANASONIC
U-14MF3E8
40,0 kW
SEER 6,7
📋 Data source: Eurovent-certified independent test data.
Eurovent certificate no. 19.02.001. Last updated: .