OUTES · Matrix A7
ORV-560TD/XR5M-A7
20 HP
56,0 kW cooling
56,0 kW heating
R410A
A efficiency
HP
Eurovent: 26.04.002
Eurovent ✓
OUTES ORV-560TD/XR5M-A7 is a heat pump VRF outdoor unit with a cooling capacity of 20 HP (56,0 kW). It uses R410A refrigerant and has SEER 5,50 / SCOP 4,07 efficiency ratings. It offers a cooling sound power of 88,0 dB(A). It is ranked #118 by SEER among 132 models in the 20 HP class (class average SEER 6,40).
20 HP class
132 models
SEER rank: 118
Class avg. SEER 6,40
Highest 8,42
Performance
| Cooling | |
|---|---|
| Nominal capacity | 56,00 kW |
| Power input | 25,45 kW |
| EER (rated) | 2,20 |
| SEER (seasonal) ℹ | 5,50 |
| Heating | |
| Nominal capacity | 56,00 kW |
| Power input | 15,47 kW |
| COP (rated) | 3,62 |
| SCOP (seasonal) ℹ | 4,07 |
| Test configuration | |
| Indoor unit combination | 8xORV-D71Q/KR5-R (Cassette) |
Physical & Environmental
| General | |
|---|---|
| System type | HP (Heat Pump) |
| Cooling type | Air-cooled |
| Combination | Possible |
| Refrigerant | R410A |
| Power supply | 400-3-50 |
| Max. indoor units | — |
| Dimensions & Weight | |
| Dimensions (H×W×D) | — × — × — mm |
| Weight | — kg |
| Sound (LwA) | |
| In cooling | 88,0 dB(A) |
| In heating | 88,0 dB(A) |
| Operating temperature | |
| Cooling range | —°C ÷ —°C |
| Heating range | —°C ÷ —°C |
📐 Ölçü bilgisi henüz girilmedi.
Bu ürünün boyut ve teknik çizim bilgileri için üreticinin teknik dokümanını inceleyebilirsiniz.
Bu ürünün boyut ve teknik çizim bilgileri için üreticinin teknik dokümanını inceleyebilirsiniz.
⚡ Energy simulation for this unit
Alternative models in the 20 HP class
Top models at the same capacity, ranked by SEER. This unit is highlighted.
8,42
8,42
8,30
8,30
8,29
8,17
5,50
◀ Smaller model
ORV-505TD/XR5M-A7
50,0 kW · SEER 5,33
Larger model ▶
ORV-615TD/XR5M-A7
61,5 kW · SEER 5,50
Other models in the same series (13 models)
❄
OUTES
ORV-255TD/XR5M-A7
25,5 kW
SEER 7,6
❄
OUTES
ORV-285TD/XR5M-A7
28,5 kW
SEER 7,5
❄
OUTES
ORV-335TD/XR5M-A7
33,5 kW
SEER 7,2
❄
OUTES
ORV-400TD/XR5M-A7
40,0 kW
SEER 6,1
❄
OUTES
ORV-450TD/XR5M-A7
45,0 kW
SEER 5,7
❄
OUTES
ORV-505TD/XR5M-A7
50,0 kW
SEER 5,3
📋 Data source: Eurovent-certified independent test data.
Eurovent certificate no. 26.04.002. Last updated: .