MDV · MV8S Series
MDVO-V8S500V2R1B
18 HP
50,0 kW cooling
50,0 kW heating
R410A
A+ efficiency
HP
Eurovent: 26.01.015
Eurovent ✓
MDV MDVO-V8S500V2R1B is a heat pump VRF outdoor unit with a cooling capacity of 18 HP (50,0 kW). It uses R410A refrigerant and has SEER 6,00 / SCOP 4,44 efficiency ratings. It offers a cooling sound power of 88,0 dB(A), a 1250×1760×580 mm body, connection for up to 29 indoor units. It is ranked #118 by SEER among 155 models in the 18 HP class (class average SEER 6,58).
18 HP class
155 models
SEER rank: 118
Class avg. SEER 6,58
Highest 8,67
Performance
| Cooling | |
|---|---|
| Nominal capacity | 50,00 kW |
| Power input | 23,81 kW |
| EER (rated) | 2,10 |
| SEER (seasonal) ℹ | 6,00 |
| Heating | |
| Nominal capacity | 50,00 kW |
| Power input | 14,49 kW |
| COP (rated) | 3,45 |
| SCOP (seasonal) ℹ | 4,44 |
| Test configuration | |
| Indoor unit combination | 4x MIH45T2N18+2x MIH80T2N18+2x MIH90T2N18 (ducted) |
Physical & Environmental
| General | |
|---|---|
| System type | HP (Heat Pump) |
| Cooling type | Air-cooled |
| Combination | Possible |
| Refrigerant | R410A |
| Power supply | 400-3-50 |
| Max. indoor units | 29 |
| Air flow | 20.000 m³/h |
| Fan count | 2 |
| Compressor count | 1 |
| Dimensions & Weight | |
| Dimensions (H×W×D) | 1760 × 1250 × 580 mm |
| Weight | 208 kg |
| Sound (LwA) | |
| In cooling | 88,0 dB(A) |
| In heating | 88,0 dB(A) |
| Sound pressure (1m) | |
| In cooling | 61,0 dB(A) |
| In heating | — |
| Operating temperature | |
| Cooling range | -15°C ÷ 55°C |
| Heating range | —°C ÷ —°C |
Üstten görünüş
Ölçüler mmYükseklik: 1.760 mm
⚡ Energy simulation for this unit
Alternative models in the 18 HP class
Top models at the same capacity, ranked by SEER. This unit is highlighted.
8,67
8,65
8,65
8,50
8,32
8,10
6,00
◀ Smaller model
MDVO-V8S450V2R1B
45,0 kW · SEER 6,05
Larger model ▶
MDVO-V8S560V2R1B
56,0 kW · SEER 5,93
Other models in the same series (8 models)
MDV
MDVO-V8S252V2R1B
25,2 kW
SEER 6,8
MDV
MDVO-V8S280V2R1B
28,0 kW
SEER 6,7
MDV
MDVO-V8S335V2R1B
33,5 kW
SEER 6,4
MDV
MDVO-V8S400V2R1B
40,0 kW
SEER 6,2
MDV
MDVO-V8S450V2R1B
45,0 kW
SEER 6,1
MDV
MDVO-V8S560V2R1B
56,0 kW
SEER 5,9
📋 Data source: Eurovent-certified independent test data.
Eurovent certificate no. 26.01.015. Last updated: .