AIRWELL · Flow Logic III
AWAU-YDV400-H13
14 HP
40,0 kW cooling
40,0 kW heating
R410A
B efficiency
HP
Eurovent: 18.06.004
Eurovent+
AIRWELL AWAU-YDV400-H13 is a heat pump VRF outdoor unit with a cooling capacity of 14 HP (40,0 kW). It uses R410A refrigerant and has SEER 4,81 / SCOP 3,51 efficiency ratings. It offers a cooling sound power of 83,0 dB(A), a 1350×1690×720 mm body, connection for up to 29 indoor units. It is ranked #165 by SEER among 166 models in the 14 HP class (class average SEER 6,77).
14 HP class
166 models
SEER rank: 165
Class avg. SEER 6,77
Highest 8,65
Performance
| Cooling | |
|---|---|
| Nominal capacity | 40,00 kW |
| Power input | 20,00 kW |
| EER (rated) | 2,00 |
| SEER (seasonal) ℹ | 4,81 |
| Heating | |
| Nominal capacity | 40,00 kW |
| Power input | 19,05 kW |
| COP (rated) | 2,10 |
| SCOP (seasonal) ℹ | 3,51 |
| Test configuration | |
| Indoor unit combination | CVTA-070N-01M22*5*CVTA-050/045N-01M22*1 (Cassette) |
Physical & Environmental
| General | |
|---|---|
| System type | HP (Heat Pump) |
| Cooling type | Air-cooled |
| Combination | Possible |
| Refrigerant | R410A |
| Power supply | 400-3-50 |
| Max. indoor units | 29 |
| Air flow | 13.200 m³/h |
| Fan count | 2 |
| Compressor count | 2 |
| Dimensions & Weight | |
| Dimensions (H×W×D) | 1690 × 1350 × 720 mm |
| Weight | 279 kg |
| Sound (LwA) | |
| In cooling | 83,0 dB(A) |
| In heating | 83,0 dB(A) |
| Sound pressure (1m) | |
| In cooling | 59,5 dB(A) |
| In heating | — |
| Operating temperature | |
| Cooling range | -5°C ÷ 50°C |
| Heating range | -23°C ÷ 21°C |
Üstten görünüş
Ölçüler mmYükseklik: 1.690 mm
⚡ Energy simulation for this unit
Alternative models in the 14 HP class
Top models at the same capacity, ranked by SEER. This unit is highlighted.
8,65
8,55
8,55
8,36
8,33
8,27
4,81
◀ Smaller model
AWAU-YDV335-H13
33,5 kW · SEER 4,81
Larger model ▶
AWAU-YDV450-H13
45,0 kW · SEER 4,81
Other models in the same series (9 models)
AIRWELL
AWAU-YDV250-H13
25,2 kW
SEER 4,8
AIRWELL
AWAU-YDV280-H13
28,0 kW
SEER 4,8
AIRWELL
AWAU-YDV335-H13
33,5 kW
SEER 4,8
AIRWELL
AWAU-YDV450-H13
45,0 kW
SEER 4,8
AIRWELL
AWAU-YDV504-H13
50,4 kW
SEER 4,8
AIRWELL
AWAU-YDV560-H13
56,0 kW
SEER 4,8
📋 Data source: Eurovent + manufacturer catalogue.
Eurovent certificate no. 18.06.004. Last updated: .