HISENSE · Hi-FLEXi S Series Heat Recovery
AVWT-76FKFSB
8 HP
22,4 kW cooling
22,4 kW heating
R410A
A++ efficiency
HR
Eurovent: 18.02.005
Eurovent ✓
HISENSE AVWT-76FKFSB is a heat recovery VRF outdoor unit with a cooling capacity of 8 HP (22,4 kW). It uses R410A refrigerant and has SEER 6,48 / SCOP 4,14 efficiency ratings. It offers a cooling sound power of 84,0 dB(A), a 950×1730×750 mm body, connection for up to 13 indoor units. It is ranked #126 by SEER among 160 models in the 8 HP class (class average SEER 7,03).
8 HP class
160 models
SEER rank: 126
Class avg. SEER 7,03
Highest 8,90
Performance
| Cooling | |
|---|---|
| Nominal capacity | 22,40 kW |
| Power input | 6,81 kW |
| EER (rated) | 3,29 |
| SEER (seasonal) ℹ | 6,48 |
| Heating | |
| Nominal capacity | 22,40 kW |
| Power input | 5,83 kW |
| COP (rated) | 3,84 |
| SCOP (seasonal) ℹ | 4,14 |
| Test configuration | |
| Indoor unit combination | AVBC-19HJDBA(R) (Cassette) |
Physical & Environmental
| General | |
|---|---|
| System type | HR (Heat Recovery) |
| Cooling type | Air-cooled |
| Combination | Possible |
| Refrigerant | R410A |
| Power supply | 400-3-50 |
| Max. indoor units | 13 |
| Air flow | 10.980 m³/h |
| Fan count | 1 |
| Compressor count | 1 |
| Dimensions & Weight | |
| Dimensions (H×W×D) | 1730 × 950 × 750 mm |
| Weight | 226 kg |
| Sound (LwA) | |
| In cooling | 84,0 dB(A) |
| In heating | 84,0 dB(A) |
| Operating temperature | |
| Cooling range | -10°C ÷ 52°C |
| Heating range | -25°C ÷ 16°C |
Üstten görünüş
Ölçüler mmYükseklik: 1.730 mm
⚡ Energy simulation for this unit
Alternative models in the 8 HP class
Top models at the same capacity, ranked by SEER. This unit is highlighted.
8,90
8,81
8,73
8,70
8,67
8,31
6,48
Other models in the same series (11 models)
HISENSE
AVWT-96FKFSB
28,0 kW
SEER 7,2
HISENSE
AVWT-114FKFSB
33,5 kW
SEER 7,2
HISENSE
AVWT-136FKFSB
40,0 kW
SEER 6,6
HISENSE
AVWT-154FKFSB
45,0 kW
SEER 6,5
HISENSE
AVWT-170FKFSB
50,0 kW
SEER 6,5
HISENSE
AVWT-190FKFSB
56,0 kW
SEER 6,4
📋 Data source: Eurovent-certified independent test data.
Eurovent certificate no. 18.02.005. Last updated: .