HISENSE · Hi-FLEXi S Series Heat Recovery
AVWT-212FKFSB
22 HP
61,5 kW cooling
61,5 kW heating
R410A
A++ efficiency
HR
Eurovent: 18.02.005
Eurovent ✓
HISENSE AVWT-212FKFSB is a heat recovery VRF outdoor unit with a cooling capacity of 22 HP (61,5 kW). It uses R410A refrigerant and has SEER 6,14 / SCOP 4,09 efficiency ratings. It offers a cooling sound power of 95,0 dB(A), a 1350×1730×750 mm body, connection for up to 36 indoor units. It is ranked #59 by SEER among 94 models in the 22 HP class (class average SEER 6,30).
22 HP class
94 models
SEER rank: 59
Class avg. SEER 6,30
Highest 7,88
Performance
| Cooling | |
|---|---|
| Nominal capacity | 61,50 kW |
| Power input | 26,74 kW |
| EER (rated) | 2,30 |
| SEER (seasonal) ℹ | 6,14 |
| Heating | |
| Nominal capacity | 61,50 kW |
| Power input | 18,75 kW |
| COP (rated) | 3,28 |
| SCOP (seasonal) ℹ | 4,09 |
| Test configuration | |
| Indoor unit combination | AVBC-27HJDBA(S) (Cassette) |
Physical & Environmental
| General | |
|---|---|
| System type | HR (Heat Recovery) |
| Cooling type | Air-cooled |
| Combination | Possible |
| Refrigerant | R410A |
| Power supply | 400-3-50 |
| Max. indoor units | 36 |
| Air flow | 17.760 m³/h |
| Fan count | 2 |
| Compressor count | 2 |
| Dimensions & Weight | |
| Dimensions (H×W×D) | 1730 × 1350 × 750 mm |
| Weight | 377 kg |
| Sound (LwA) | |
| In cooling | 95,0 dB(A) |
| In heating | 95,0 dB(A) |
| Operating temperature | |
| Cooling range | -10°C ÷ 52°C |
| Heating range | -25°C ÷ 16°C |
Üstten görünüş
Ölçüler mmYükseklik: 1.730 mm
⚡ Energy simulation for this unit
Alternative models in the 22 HP class
Top models at the same capacity, ranked by SEER. This unit is highlighted.
7,88
7,53
7,27
7,23
7,20
7,01
6,14
Other models in the same series (11 models)
HISENSE
AVWT-76FKFSB
22,4 kW
SEER 6,5
HISENSE
AVWT-96FKFSB
28,0 kW
SEER 7,2
HISENSE
AVWT-114FKFSB
33,5 kW
SEER 7,2
HISENSE
AVWT-136FKFSB
40,0 kW
SEER 6,6
HISENSE
AVWT-154FKFSB
45,0 kW
SEER 6,5
HISENSE
AVWT-170FKFSB
50,0 kW
SEER 6,5
📋 Data source: Eurovent-certified independent test data.
Eurovent certificate no. 18.02.005. Last updated: .