HISENSE · Hi-FLEXi S Series Heat Recovery(High Efficiency)
AVWT-114FKFSHA
12 HP
33,5 kW cooling
33,5 kW heating
R410A
A+++ efficiency
HR
Eurovent: 18.02.005
Eurovent ✓
HISENSE AVWT-114FKFSHA is a heat recovery VRF outdoor unit with a cooling capacity of 12 HP (33,5 kW). It uses R410A refrigerant and has SEER 8,56 / SCOP 4,24 efficiency ratings. It offers a cooling sound power of 86,0 dB(A), a 950×1730×750 mm body, connection for up to 19 indoor units. It is ranked #3 by SEER among 200 models in the 12 HP class (class average SEER 6,79).
12 HP class
200 models
SEER rank: 3
Class avg. SEER 6,79
Highest 8,85
Performance
| Cooling | |
|---|---|
| Nominal capacity | 33,50 kW |
| Power input | 7,25 kW |
| EER (rated) | 4,62 |
| SEER (seasonal) ℹ | 8,56 |
| Heating | |
| Nominal capacity | 33,50 kW |
| Power input | 6,20 kW |
| COP (rated) | 5,40 |
| SCOP (seasonal) ℹ | 4,24 |
| Test configuration | |
| Indoor unit combination | AVBC-19HJDBA(R) (Cassette) |
Physical & Environmental
| General | |
|---|---|
| System type | HR (Heat Recovery) |
| Cooling type | Air-cooled |
| Combination | Possible |
| Refrigerant | R410A |
| Power supply | 400-3-50 |
| Max. indoor units | 19 |
| Air flow | 10.980 m³/h |
| Fan count | 1 |
| Compressor count | 1 |
| Dimensions & Weight | |
| Dimensions (H×W×D) | 1730 × 950 × 750 mm |
| Weight | 246 kg |
| Sound (LwA) | |
| In cooling | 86,0 dB(A) |
| In heating | 86,0 dB(A) |
| Operating temperature | |
| Cooling range | -10°C ÷ 52°C |
| Heating range | -25°C ÷ 16°C |
Üstten görünüş
Ölçüler mmYükseklik: 1.730 mm
⚡ Energy simulation for this unit
Alternative models in the 12 HP class
Top models at the same capacity, ranked by SEER. This unit is highlighted.
8,85
8,81
8,56
8,23
8,11
8,09
7,94
Other models in the same series (8 models)
HISENSE
AVWT-76FKFSHA
22,4 kW
SEER 8,7
HISENSE
AVWT-96FKFSHA
28,0 kW
SEER 7,9
HISENSE
AVWT-136FKFSHA
40,0 kW
SEER 8,4
HISENSE
AVWT-154FKFSHA
45,0 kW
SEER 8,0
HISENSE
AVWT-170FKFSHA
50,0 kW
SEER 8,0
HISENSE
AVWT-190FKFSHA
56,0 kW
SEER 7,7
📋 Data source: Eurovent-certified independent test data.
Eurovent certificate no. 18.02.005. Last updated: .