HAIER · MRV S II
AU12NFKERA
11 HP
31,5 kW cooling
31,5 kW heating
R410A
A efficiency
HP
Eurovent: 18.06.003
Eurovent ✓
HAIER AU12NFKERA is a heat pump VRF outdoor unit with a cooling capacity of 11 HP (31,5 kW). It uses R410A refrigerant and has SEER 5,46 / SCOP 3,77 efficiency ratings. It offers a cooling sound power of 85,0 dB(A). It is ranked #6 by SEER among 12 models in the 11 HP class (class average SEER 5,99).
11 HP class
12 models
SEER rank: 6
Class avg. SEER 5,99
Highest 7,50
Performance
| Cooling | |
|---|---|
| Nominal capacity | 31,50 kW |
| Power input | 12,86 kW |
| EER (rated) | 2,45 |
| SEER (seasonal) ℹ | 5,46 |
| Heating | |
| Nominal capacity | 31,50 kW |
| Power input | 9,46 kW |
| COP (rated) | 3,33 |
| SCOP (seasonal) ℹ | 3,77 |
| Test configuration | |
| Indoor unit combination | 6xAB182MRERA (Cassette) |
Physical & Environmental
| General | |
|---|---|
| System type | HP (Heat Pump) |
| Cooling type | Air-cooled |
| Combination | Possible |
| Refrigerant | R410A |
| Power supply | 400-3-50 |
| Max. indoor units | — |
| Dimensions & Weight | |
| Dimensions (H×W×D) | — × — × — mm |
| Weight | — kg |
| Sound (LwA) | |
| In cooling | 85,0 dB(A) |
| In heating | 87,0 dB(A) |
| Operating temperature | |
| Cooling range | —°C ÷ —°C |
| Heating range | —°C ÷ —°C |
📐 Ölçü bilgisi henüz girilmedi.
Bu ürünün boyut ve teknik çizim bilgileri için üreticinin teknik dokümanını inceleyebilirsiniz.
Bu ürünün boyut ve teknik çizim bilgileri için üreticinin teknik dokümanını inceleyebilirsiniz.
⚡ Energy simulation for this unit
Alternative models in the 11 HP class
Top models at the same capacity, ranked by SEER. This unit is highlighted.
7,50
7,50
7,47
5,68
5,68
5,46
5,46
Other models in the same series (11 models)
❄
HAIER
AU04IFPERA
12,1 kW
SEER 6,8
❄
HAIER
AU042FPERA
12,1 kW
SEER 6,8
❄
HAIER
AU042FNERA
12,1 kW
SEER 4,8
❄
HAIER
AU05IFPERA
14,0 kW
SEER 6,7
❄
HAIER
AU052FPERA
14,0 kW
SEER 6,7
❄
HAIER
AU052FNERA
14,0 kW
SEER 4,8
📋 Data source: Eurovent-certified independent test data.
Eurovent certificate no. 18.06.003. Last updated: .