LG · MULTI V 5
ARUM160LTE5
16 HP
44,8 kW cooling
44,8 kW heating
R410A
A++ efficiency
HP
HR capable
Eurovent: 14.12.005
Eurovent ✓
LG ARUM160LTE5 is a heat pump VRF outdoor unit with a cooling capacity of 16 HP (44,8 kW). It uses R410A refrigerant and has SEER 7,74 / SCOP 5,30 efficiency ratings. It offers a cooling sound power of 86,0 dB(A), a 1240×1690×760 mm body, connection for up to 26 indoor units. It is ranked #10 by SEER among 167 models in the 16 HP class (class average SEER 6,61).
16 HP class
167 models
SEER rank: 10
Class avg. SEER 6,61
Highest 8,93
Performance
| Cooling | |
|---|---|
| Nominal capacity | 44,80 kW |
| Power input | 17,23 kW |
| EER (rated) | 2,60 |
| SEER (seasonal) ℹ | 7,74 |
| Heating | |
| Nominal capacity | 44,80 kW |
| Power input | 10,59 kW |
| COP (rated) | 4,23 |
| SCOP (seasonal) ℹ | 5,30 |
| Test configuration | |
| Indoor unit combination | 2 x ARNU24GTAA4 / 4 x ARNU28GTAA4 (cassette) |
Physical & Environmental
| General | |
|---|---|
| System type | HP (Heat Pump · can also operate as heat recovery) |
| Cooling type | Air-cooled |
| Combination | Possible |
| Refrigerant | R410A |
| Power supply | 400-3-50 |
| Max. indoor units | 26 |
| Air flow | 19.200 m³/h |
| Fan count | 2 |
| Compressor count | 1 |
| Dimensions & Weight | |
| Dimensions (H×W×D) | 1690 × 1240 × 760 mm |
| Weight | 237 kg |
| Sound (LwA) | |
| In cooling | 86,0 dB(A) |
| In heating | 86,0 dB(A) |
| Sound pressure (1m) | |
| In cooling | 60,5 dB(A) |
| In heating | 61,5 dB(A) |
| Operating temperature | |
| Cooling range | -10°C ÷ 48°C |
| Heating range | -25°C ÷ 18°C |
Üstten görünüş
Ölçüler mmYükseklik: 1.690 mm
⚡ Energy simulation for this unit
Alternative models in the 16 HP class
Top models at the same capacity, ranked by SEER. This unit is highlighted.
8,93
8,64
8,45
8,02
7,99
7,98
7,74
Other models in the same series (7 models)
LG
ARUM080LTE5
22,4 kW
SEER 7,9
LG
ARUM100LTE5
28,0 kW
SEER 7,8
LG
ARUM120LTE5
33,6 kW
SEER 7,7
LG
ARUM140LTE5
39,2 kW
SEER 8,2
LG
ARUM180LTE5
50,4 kW
SEER 8,5
LG
ARUM200LTE5
56,0 kW
SEER 8,2
📋 Data source: Eurovent-certified independent test data.
Eurovent certificate no. 14.12.005. Last updated: .