Fujitsu Atlantic · VRF Max 4 R (V R-IV)
AJY126GALDH
14 HP
40,0 kW cooling
40,0 kW heating
R410A
A++ efficiency
HR
Eurovent: 15.06.012
Eurovent ✓
Fujitsu Atlantic AJY126GALDH is a heat recovery VRF outdoor unit with a cooling capacity of 14 HP (40,0 kW). It uses R410A refrigerant and has SEER 6,76 / SCOP 4,31 efficiency ratings. It offers a cooling sound power of 82,0 dB(A), a 1240×1690×765 mm body, connection for up to 30 indoor units. It is ranked #71 by SEER among 166 models in the 14 HP class (class average SEER 6,77).
14 HP class
166 models
SEER rank: 71
Class avg. SEER 6,77
Highest 8,65
Performance
| Cooling | |
|---|---|
| Nominal capacity | 40,00 kW |
| Power input | 13,38 kW |
| EER (rated) | 2,99 |
| SEER (seasonal) ℹ | 6,76 |
| Heating | |
| Nominal capacity | 40,00 kW |
| Power input | 10,53 kW |
| COP (rated) | 3,80 |
| SCOP (seasonal) ℹ | 4,31 |
| Test configuration | |
| Indoor unit combination | ARXP018GLFH x4 + ARXP030GLFH x2 (Ducted) |
Physical & Environmental
| General | |
|---|---|
| System type | HR (Heat Recovery) |
| Cooling type | Air-cooled |
| Combination | Possible |
| Refrigerant | R410A |
| Power supply | 400-3-50 |
| Max. indoor units | 30 |
| Air flow | 13.000 m³/h |
| Fan count | 1 |
| Compressor count | 1 |
| Dimensions & Weight | |
| Dimensions (H×W×D) | 1690 × 1240 × 765 mm |
| Weight | 286 kg |
| Sound (LwA) | |
| In cooling | 82,0 dB(A) |
| In heating | 83,0 dB(A) |
| Sound pressure (1m) | |
| In cooling | 60,0 dB(A) |
| In heating | 62,0 dB(A) |
| Operating temperature | |
| Cooling range | -10°C ÷ 46°C |
| Heating range | -20°C ÷ 16°C |
Üstten görünüş
Ölçüler mmYükseklik: 1.690 mm
⚡ Energy simulation for this unit
Alternative models in the 14 HP class
Top models at the same capacity, ranked by SEER. This unit is highlighted.
8,65
8,55
8,55
8,36
8,33
8,27
6,76
Other models in the same series (5 models)
Fujitsu Atlantic
AJY072GALDH
22,4 kW
SEER 7,2
Fujitsu Atlantic
AJY090GALDH
28,0 kW
SEER 6,6
Fujitsu Atlantic
AJY108GALDH
33,5 kW
SEER 6,7
Fujitsu Atlantic
AJY144GALDH
45,0 kW
SEER 6,3
📋 Data source: Eurovent-certified independent test data.
Eurovent certificate no. 15.06.012. Last updated: .