Fujitsu Atlantic · VRF Max 4 (V-IV)
AJY108LALDH
12 HP
33,5 kW cooling
33,5 kW heating
R410A
A++ efficiency
HP
Eurovent: 15.06.012
Eurovent ✓
Fujitsu Atlantic AJY108LALDH is a heat pump VRF outdoor unit with a cooling capacity of 12 HP (33,5 kW). It uses R410A refrigerant and has SEER 7,33 / SCOP 4,19 efficiency ratings. It offers a cooling sound power of 81,0 dB(A), a 1240×1690×765 mm body, connection for up to 26 indoor units. It is ranked #25 by SEER among 200 models in the 12 HP class (class average SEER 6,79).
12 HP class
200 models
SEER rank: 25
Class avg. SEER 6,79
Highest 8,85
Performance
| Cooling | |
|---|---|
| Nominal capacity | 33,50 kW |
| Power input | 9,23 kW |
| EER (rated) | 3,63 |
| SEER (seasonal) ℹ | 7,33 |
| Heating | |
| Nominal capacity | 33,50 kW |
| Power input | 7,51 kW |
| COP (rated) | 4,46 |
| SCOP (seasonal) ℹ | 4,19 |
| Test configuration | |
| Indoor unit combination | ARXP018GLFH x6 (Ducted) |
Physical & Environmental
| General | |
|---|---|
| System type | HP (Heat Pump) |
| Cooling type | Air-cooled |
| Combination | Possible |
| Refrigerant | R410A |
| Power supply | 400-3-50 |
| Max. indoor units | 26 |
| Air flow | 13.000 m³/h |
| Fan count | 1 |
| Compressor count | 1 |
| Dimensions & Weight | |
| Dimensions (H×W×D) | 1690 × 1240 × 765 mm |
| Weight | 275 kg |
| Sound (LwA) | |
| In cooling | 81,0 dB(A) |
| In heating | 83,0 dB(A) |
| Sound pressure (1m) | |
| In cooling | 58,0 dB(A) |
| In heating | 60,0 dB(A) |
| Operating temperature | |
| Cooling range | -15°C ÷ 46°C |
| Heating range | -20°C ÷ 16°C |
Üstten görünüş
Ölçüler mmYükseklik: 1.690 mm
⚡ Energy simulation for this unit
Alternative models in the 12 HP class
Top models at the same capacity, ranked by SEER. This unit is highlighted.
8,85
8,81
8,56
8,23
8,11
8,09
7,33
Other models in the same series (5 models)
Fujitsu Atlantic
AJY072LALDH
22,4 kW
SEER 7,1
Fujitsu Atlantic
AJY090LALDH
28,0 kW
SEER 6,6
Fujitsu Atlantic
AJY126LALDH
40,0 kW
SEER 6,7
Fujitsu Atlantic
AJY144LALDH
45,0 kW
SEER 6,2
📋 Data source: Eurovent-certified independent test data.
Eurovent certificate no. 15.06.012. Last updated: .