FUJITSU · J-VL
AJY108KELAH
12 HP
33,5 kW cooling
33,5 kW heating
R32
Mini VRF
A++ efficiency
HP
Eurovent: 15.06.012
Eurovent ✓
FUJITSU AJY108KELAH is a heat pump VRF outdoor unit with a cooling capacity of 12 HP (33,5 kW). It uses R32 refrigerant and has SEER 7,57 / SCOP 4,67 efficiency ratings. It offers a cooling sound power of 73,0 dB(A), a 1080×1428×480 mm body, connection for up to 30 indoor units. It is ranked #17 by SEER among 200 models in the 12 HP class (class average SEER 6,79).
12 HP class
200 models
SEER rank: 17
Class avg. SEER 6,79
Highest 8,85
Performance
| Cooling | |
|---|---|
| Nominal capacity | 33,50 kW |
| Power input | 9,46 kW |
| EER (rated) | 3,54 |
| SEER (seasonal) ℹ | 7,57 |
| Heating | |
| Nominal capacity | 33,50 kW |
| Power input | 7,25 kW |
| COP (rated) | 4,62 |
| SCOP (seasonal) ℹ | 4,67 |
| Test configuration | |
| Indoor unit combination | ARXP018HTBH x6 (Ducted) |
Physical & Environmental
| General | |
|---|---|
| System type | HP (Heat Pump) |
| Cooling type | Air-cooled |
| Combination | Not possible |
| Refrigerant | R32 |
| Power supply | 400-3-50 |
| Max. indoor units | 30 |
| Air flow | 11.000 m³/h |
| Fan count | 2 |
| Compressor count | 1 |
| Dimensions & Weight | |
| Dimensions (H×W×D) | 1428 × 1080 × 480 mm |
| Weight | 178 kg |
| Sound (LwA) | |
| In cooling | 73,0 dB(A) |
| In heating | 75,0 dB(A) |
| Sound pressure (1m) | |
| In cooling | 58,0 dB(A) |
| In heating | 62,0 dB(A) |
| Operating temperature | |
| Cooling range | -15°C ÷ 46°C |
| Heating range | -20°C ÷ 16°C |
Üstten görünüş
Ölçüler mmYükseklik: 1.428 mm
⚡ Energy simulation for this unit
Alternative models in the 12 HP class
Top models at the same capacity, ranked by SEER. This unit is highlighted.
8,85
8,81
8,56
8,23
8,11
8,09
7,57
Other models in the same series (6 models)
FUJITSU
AJY072KELAH
22,4 kW
SEER 8,0
FUJITSU
AJY090KELAH
28,0 kW
SEER 7,7
FUJITSU
AJY126KELAH
40,0 kW
SEER 7,2
FUJITSU
AJY144KELAH
45,0 kW
SEER 7,0
FUJITSU
AJY162KELAH
50,0 kW
SEER 6,6
📋 Data source: Eurovent-certified independent test data.
Eurovent certificate no. 15.06.012. Last updated: .